N2XH 4x50 mm2

Description

Description

Standards

  • Product
    IEC 60502-1

Application:

Used in energy networks in hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire

 

Construction:

  1. Conductor:Copper
  2. Insulation:XLPE
  3. Filler:LSZH
  4. Outer sheath:LSZH

 

Marking:

NEXANS IEC 60502 N2XH Number of cores x cross section 0.6/1 kV "YEAR" 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular stranded (RM)
With smaller neutral conductor
No
Insulation
XLPE (chemical)
Outer sheath
HFFR (Halogen Free Flame Retardant)
Halogen free
EN 60754-2
Conductor flexibility
Stranded class 2
Core identification
Blue, brown, black, grey
Sheath colour
Black
With Green/Yellow core

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
50 mm²
Neutral conductor section (when smaller)
- mm²
Nominal outer diameter
29.0 mm
Approximate weight
2250 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
0.387 Ohm/km
Permissible current rating in open air
192 A
Permissible current rating when buried
153 A

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
8 (xD)
Flame retardant
EN 60332-1-2
Fire retardant
EN 50399
Smoke density
EN/IEC 61034-2
Gases corrosivity
IEC/EN 60754-2
Max. conductor temperature in service
90 °C

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1000626-TRDE
  • Certification Date : 1/28/21
  • AVCP (Assessment and Verification of Constancy of Performance) : System 1+
  • Notified body : 1008
  • Declared performance : Cca-s1,d2,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close