N2XH FE 180 Single Core Cables

Products

N2XH FE 180 1x4 mm2

Nexans ref. 10530786 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 80 kg/km
  • Conductor cross-section: 4 mm²
  • Nominal outer diameter: 6.9 mm
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 39 A
  • Perm. current rating in air 30°C - trefoil formation: - A

 

N2XH FE 180 1x6 mm2

Nexans ref. 10530992 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 100 kg/km
  • Conductor cross-section: 6 mm²
  • Nominal outer diameter: 7.5 mm
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 49 A
  • Perm. current rating in air 30°C - trefoil formation: - A

 

N2XH FE 180 1x10 mm2

Nexans ref. 10517201 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 140 kg/km
  • Conductor cross-section: 10 mm²
  • Nominal outer diameter: 7.9 mm
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 65 A
  • Perm. current rating in air 30°C - trefoil formation: - A

 

N2XH FE 180 1x16 mm2

Nexans ref. 10518556 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 190 kg/km
  • Conductor cross-section: 16 mm²
  • Nominal outer diameter: 8.9 mm
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 84 A
  • Perm. current rating in air 30°C - trefoil formation: - A

 

N2XH FE 180 1x25 mm2

Nexans ref. 10517203 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 300 kg/km
  • Conductor cross-section: 25 mm²
  • Nominal outer diameter: 11.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 107 A
  • Perm. current rating in air 30°C - trefoil formation: 135 A

 

N2XH FE 180 1x35 mm2

Nexans ref. 10518555 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 380 kg/km
  • Conductor cross-section: 35 mm²
  • Nominal outer diameter: 11.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 129 A
  • Perm. current rating in air 30°C - trefoil formation: 169 A

 

N2XH FE 180 1x50 mm2

Nexans ref. 10518554 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 500 kg/km
  • Conductor cross-section: 50 mm²
  • Nominal outer diameter: 13.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 153 A
  • Perm. current rating in air 30°C - trefoil formation: 207 A

 

N2XH FE 180 1x70 mm2

Nexans ref. 10518553 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 700 kg/km
  • Conductor cross-section: 70 mm²
  • Nominal outer diameter: 15.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 188 A
  • Perm. current rating in air 30°C - trefoil formation: 268 A

 

N2XH FE 180 1x95 mm2

Nexans ref. 10518552 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 950 kg/km
  • Conductor cross-section: 95 mm²
  • Nominal outer diameter: 17.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 226 A
  • Perm. current rating in air 30°C - trefoil formation: 328 A

 

N2XH FE 180 1x120 mm2

Nexans ref. 10518551 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 1200 kg/km
  • Conductor cross-section: 120 mm²
  • Nominal outer diameter: 19.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 257 A
  • Perm. current rating in air 30°C - trefoil formation: 383 A

 

N2XH FE 180 1x150 mm2

Nexans ref. 10518550 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 1500 kg/km
  • Conductor cross-section: 150 mm²
  • Nominal outer diameter: 20.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 287 A
  • Perm. current rating in air 30°C - trefoil formation: 444 A

 

N2XH FE 180 1x185 mm2

Nexans ref. 10518549 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 1800 kg/km
  • Conductor cross-section: 185 mm²
  • Nominal outer diameter: 22.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.099 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 324 A
  • Perm. current rating in air 30°C - trefoil formation: 510 A

 

N2XH FE 180 1x240 mm2

Nexans ref. 10518548 - Country ref. TR

  • Packaging: Drum (1000m)
  • Approximate weight: 2500 kg/km
  • Conductor cross-section: 240 mm²
  • Nominal outer diameter: 25.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 375 A
  • Perm. current rating in air 30°C - trefoil formation: 607 A

 

Description

Description

Standards

  • Product
    IEC 60502-1

Application

Refineries,mines,hotels,schools, tunnels, high constructions hospitals,power plants,data processing centers, business centers where there is a risk of fire.

Construction

  1. Conductor:Copper
  2. Fire proof:Mica tape
  3. Insulation:XLPE
  4. Outher sheath:LSZH (Low smoke zero halogen)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Stranded class 2
Conductor material
Copper
Conductor shape
Circular stranded (RM)
Core identification
Black
Halogen free
IEC 60754-1
Insulation
XLPE (chemical)
Outer sheath
HFFR (Halogen Free Flame Retardant)
Sheath colour
Orange

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Fire resistant
IEC 60331-21
Flame retardant
IEC 60332-3 Cat. C
Gases corrosivity
IEC 60754-2
Max. conductor temperature in service
90 °C
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Smoke density
IEC 61034

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close