N2XRH FE 180 4x150 mm2
N2XRH FE 180 4x150 mm2
Fire-resistant, multi-core, single or multi-wire copper conductor power cables with galvanized round steel wire armoring, halogen-free and fire-safe. Thanks to their low smoke density, non-flame propagating properties and no corrosive gas emissions for protecting life and property in case of fire. Their armored design provides resistance to mechanical external impacts. They maintain circuit integrity for 180 minutes during a fire (FE 180).
Read more- Country ref. : TR
Description
Description
Standards
-
ProductIEC 60502-1
Application
- Places where there is a risk of fire and where precautions must be taken against fire.
- Applications where there are mechanical strains
Construction
- Conductor:Copper
- Fire proof:Mica tape
- Insulation:XLPE
- Filler:LSZH (Low Smoke Zero Halogen)
- Armour (Steel wire)
- Outer sheath:LSZH (Low Smoke Zero Halogen)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Circular stranded (RM)
Insulation
XLPE (Cross-linked Polyethylene)
Outer sheath
LSZH
Halogen free
IEC 60754-1
Armour type
Steel wires
Conductor flexibility
-
Core identification
Blue, brown, black, grey
Sheath colour
Orange
Dimensional characteristics
Dimensional characteristics
Number of cores
4
Conductor cross-section
150 mm²
Nominal outer diameter
54.0 mm
Approximate weight
8500 kg/km
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
0.124 Ohm/km
Permissible current rating in open air
399 A
Permissible current rating when buried
287 A
Usage characteristics
Usage characteristics
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
8 (xD)
Flame retardant
IEC 60332-3 Cat. C
Smoke density
IEC 61034
Gases corrosivity
IEC 60754-2
Fire resistant
IEC 60331-21
Max. conductor temperature in service
90 °C
Resources