NA2XH Single Core Cables Eca Class

Products

NA2XH 1x95 mm2

Nexans ref. 10571341 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 95 mm²
  • Nominal outer diameter: 16.0 mm
  • Approximate weight: 370 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 172 A
  • Perm. current rating in air 30°C - trefoil formation: 332 A

 

NA2XH 1x120 mm2

Nexans ref. 10571340 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 120 mm²
  • Nominal outer diameter: 18.0 mm
  • Approximate weight: 450 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 197 A
  • Perm. current rating in air 30°C - trefoil formation: 387 A

 

NA2XH 1x150 mm2

Nexans ref. 10571339 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 150 mm²
  • Nominal outer diameter: 20.0 mm
  • Approximate weight: 560 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 220 A
  • Perm. current rating in air 30°C - trefoil formation: 448 A

 

NA2XH 1x185 mm2

Nexans ref. 10571338 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 185 mm²
  • Nominal outer diameter: 22.0 mm
  • Approximate weight: 690 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 250 A
  • Perm. current rating in air 30°C - trefoil formation: 515 A

 

NA2XH 1x240 mm2

Nexans ref. 10571337 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 240 mm²
  • Nominal outer diameter: 25.0 mm
  • Approximate weight: 870 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 290 A
  • Perm. current rating in air 30°C - trefoil formation: 611 A

 

Description

Description

Standards

  • Product
    IEC 60502-1

Application

Used in energy networks in hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire

Construction

  1. Conductor:Aluminium
  2. Insulation:XLPE
  3. Outer sheath:LSZH

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular stranded (RM)
Insulation
XLPE (Cross-linked Polyethylene)
Outer sheath
LSZH
Halogen free
IEC 60754-1
Core identification
Black
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
12 (xD)
Flame retardant
IEC 60332-3 Cat. C
Smoke density
IEC 61034
Gases corrosivity
IEC 60754-2
Max. conductor temperature in service
90 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close