CU/XLPE/AWA/LSZH BS 6724 Cca Class

Products

CU/XLPE/AWA/LSZH 1x50 mm2

Nexans ref. 10546190 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 50 mm²
  • Outer Diameter: 16 mm
  • Approximate weight: 600 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 288 A
  • Permissible current rating clipped direct: 220 A
  • Permissible short circuit current conductor 1s: 7.2 kA

 

CU/XLPE/AWA/LSZH 1x70 mm2

Nexans ref. 10546191 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 70 mm²
  • Outer Diameter: 19 mm
  • Approximate weight: 900 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 358 A
  • Permissible current rating clipped direct: 277 A
  • Permissible short circuit current conductor 1s: 10 kA

 

CU/XLPE/AWA/LSZH 1x95 mm2

Nexans ref. 10546192 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 95 mm²
  • Outer Diameter: 20 mm
  • Approximate weight: 1200 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 425 A
  • Permissible current rating clipped direct: 333 A
  • Permissible short circuit current conductor 1s: 13.6 kA

 

CU/XLPE/AWA/LSZH 1x120 mm2

Nexans ref. 10546193 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 120 mm²
  • Outer Diameter: 22 mm
  • Approximate weight: 1400 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 485 A
  • Permissible current rating clipped direct: 383 A
  • Permissible short circuit current conductor 1s: 17.2 kA

 

CU/XLPE/AWA/LSZH 1x150 mm2

Nexans ref. 10546194 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 150 mm²
  • Outer Diameter: 25 mm
  • Approximate weight: 1800 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 549 A
  • Permissible current rating clipped direct: 437 A
  • Permissible short circuit current conductor 1s: 21.4 kA

 

CU/XLPE/AWA/LSZH 1x185 mm2

Nexans ref. 10546195 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 185 mm²
  • Outer Diameter: 27 mm
  • Approximate weight: 2250 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.099 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 618 A
  • Permissible current rating clipped direct: 496 A
  • Permissible short circuit current conductor 1s: 26.5 kA

 

CU/XLPE/AWA/LSZH 1x240 mm2

Nexans ref. 10546196 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 240 mm²
  • Outer Diameter: 30 mm
  • Approximate weight: 2750 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 715 A
  • Permissible current rating clipped direct: 579 A
  • Permissible short circuit current conductor 1s: 34.3 kA

 

CU/XLPE/AWA/LSZH 1x300 mm2

Nexans ref. 10546197 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 300 mm²
  • Outer Diameter: 32 mm
  • Approximate weight: 3500 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.06 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 810 A
  • Permissible current rating clipped direct: 662 A
  • Permissible short circuit current conductor 1s: 42.9 kA

 

CU/XLPE/AWA/LSZH 1x400 mm2

Nexans ref. 10546198 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 400 mm²
  • Outer Diameter: 36 mm
  • Approximate weight: 4250 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 848 A
  • Permissible current rating clipped direct: 717 A
  • Permissible short circuit current conductor 1s: 57.2 kA

 

CU/XLPE/AWA/LSZH 1x500 mm2

Nexans ref. 10546199 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 500 mm²
  • Outer Diameter: 40 mm
  • Approximate weight: 5500 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.037 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 923 A
  • Permissible current rating clipped direct: 791 A
  • Permissible short circuit current conductor 1s: 71.5 kA

 

CU/XLPE/AWA/LSZH 1x630 mm2

Nexans ref. 10546200 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 630 mm²
  • Outer Diameter: 45 mm
  • Approximate weight: 6750 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.028 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 992 A
  • Permissible current rating clipped direct: 861 A
  • Permissible short circuit current conductor 1s: 90.1 kA

 

CU/XLPE/AWA/LSZH 1x800 mm2

Nexans ref. 10546201 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 800 mm²
  • Outer Diameter: 53 mm
  • Approximate weight: 9000 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.022 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 1042 A
  • Permissible current rating clipped direct: 904 A
  • Permissible short circuit current conductor 1s: 114.4 kA

 

CU/XLPE/AWA/LSZH 1x1000 mm2

Nexans ref. 10546202 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 1000 mm²
  • Outer Diameter: 58 mm
  • Approximate weight: 11000 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.018 Ohm/km
  • Perm. current rating in air 30°C - flat formation: 1110 A
  • Permissible current rating clipped direct: 961 A
  • Permissible short circuit current conductor 1s: 143 kA

 

Description

Description

Standards

  • Product
    BS 6724; IEC 60502

Application

Used in energy networks in hotels, schools, tunnels, high constructions,hospitals, power plants, data processing centers, business centers where there is a risk of fire

Construction

  1. Conductor:Copper
  2. Insulation:XLPE
  3. Inner sheath:LSZH
  4. Armour:Single layer Aluminium wire
  5. Outer sheath:LSZH

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor shape
Circular stranded (RM)
Conductor material
Copper
Insulation
XLPE (Cross-linked Polyethylene)
Core identification
Brown
Armour type
Aluminium Wire
Outer sheath
LSZH
Conductor flexibility
Stranded class 2
Halogen free
IEC 60754-1
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Usage characteristics

Usage characteristics

Short-circuit max. conductor temperature
250 °C
Operating temperature, range
-20 ... 60 °C
Bending factor when laying
15 (xD)
Flame retardant
IEC 60332-3 Cat. C
Gases corrosivity
IEC 60754-2
Max. conductor temperature in service
90 °C
Smoke density
IEC 61034
U.V resistance
Yes

Resources

Resources

Current capacity table XLPE insulation single core three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium –

Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground

Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air F Single-core trefoil cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
1.5 17.0 0.0 20.0 0.0 22.0 0.0 21.0 0.0 23.0 0.0 0.0 0.0 0.0 0.0
2.5 23.0 19.0 28.0 22.0 30.0 24.0 28.0 22.0 30.0 0.0 0.0 0.0 0.0 0.0
4.0 31.0 25.0 37.0 29.0 40.0 32.0 36.0 28.0 39.0 0.0 0.0 0.0 0.0 0.0
6.0 40.0 32.0 48.0 38.0 52.0 41.0 44.0 35.0 49.0 0.0 0.0 0.0 0.0 0.0
10.0 54.0 44.0 66.0 52.0 71.0 57.0 58.0 46.0 65.0 0.0 0.0 0.0 0.0 0.0
16.0 73.0 58.0 88.0 71.0 96.0 76.0 75.0 59.0 84.0 64.0 0.0 0.0 0.0 0.0
25.0 95.0 76.0 117.0 93.0 119.0 90.0 96.0 75.0 107.0 82.0 141.0 107.0 135.0 103.0
35.0 117.0 94.0 144.0 116.0 147.0 112.0 115.0 90.0 129.0 98.0 176.0 135.0 169.0 129.0
50.0 141.0 113.0 175.0 140.0 179.0 136.0 135.0 106.0 153.0 117.0 216.0 165.0 207.0 159.0
70.0 179.0 142.0 222.0 179.0 229.0 174.0 167.0 130.0 188.0 144.0 279.0 215.0 268.0 206.0
95.0 216.0 171.0 269.0 217.0 278.0 211.0 197.0 154.0 226.0 172.0 342.0 264.0 328.0 253.0
120.0 249.0 197.0 312.0 251.0 322.0 245.0 223.0 174.0 257.0 197.0 400.0 308.0 383.0 296.0
150.0 285.0 226.0 342.0 267.0 371.0 283.0 251.0 197.0 287.0 220.0 464.0 358.0 444.0 343.0
185.0 324.0 256.0 384.0 300.0 424.0 323.0 281.0 220.0 324.0 250.0 533.0 413.0 510.0 395.0
240.0 380.0 300.0 450.0 351.0 500.0 382.0 324.0 253.0 375.0 290.0 634.0 492.0 607.0 471.0
300.0 435.0 344.0 514.0 402.0 576.0 440.0 365.0 286.0 419.0 326.0 736.0 571.0 703.0 547.0
400.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 868.0 694.0 823.0 663.0
500.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 998.0 806.0 946.0 770.0
630.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1151.0 942.0 1088.0 899.0

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close