N2XH Multi Core Cables Dca Class
N2XH Multi Core Cables Dca Class
0.6/1 kV XLPE insulated multi core, halogen free, flame retardant cableS
Read moreN2XH 3x1.5 mm2
Nexans ref. 10549395 - Country ref. TR
- Packaging: Drum (1000m)
- Conductor cross-section: 1.5 mm²
- Nominal outer diameter: 10.0 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Permissible current rating in open air: 23 A
- Permissible current rating when buried: 21 A
N2XH 3x2.5 mm2
Nexans ref. 10549396 - Country ref. TR
- Packaging: Drum (1000m)
- Conductor cross-section: 2.5 mm²
- Nominal outer diameter: 11.0 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Permissible current rating in open air: 32 A
- Permissible current rating when buried: 28 A
Description
Description
Standards
-
ProductIEC 60502-1
Application
Used in energy networks in hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire
Construction
- Conductor:Copper
- Insulation:XLPE
- Filler:LSZH
- Outer sheath:LSZH
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Circular solid (RE)
With smaller neutral conductor
No
Insulation
XLPE (chemical)
Outer sheath
HFFR (Halogen Free Flame Retardant)
Halogen free
IEC 60754-1
Conductor flexibility
Solid class 1
Core identification
Brown, black, grey
Sheath colour
Black
With Green/Yellow core
No
Dimensional characteristics
Dimensional characteristics
Number of cores
3
Approximate weight
140 kg/km
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Usage characteristics
Usage characteristics
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
8 (xD)
Flame retardant
IEC 60332-3 Cat. C
Smoke density
IEC 61034
Gases corrosivity
IEC 60754-2
Max. conductor temperature in service
90 °C