NA2XH Multi Core Cables - Eca Class
NA2XH Multi Core Cables - Eca Class
0.6/1 kV XLPE insulated multi core, halogen free, flame retardant cables with aluminium conductor
Read moreNA2XH 3x25 mm2
Nexans ref. 10588764 - Country ref. TR
- Packaging: Drum
- Core identification: Brown, black, grey
- Number of cores: 3
- Conductor cross-section: 25 mm²
- Nominal outer diameter: 20.4 mm
- Approximate weight: 550 kg/km
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Permissible current rating in open air: 97 A
- Permissible current rating when buried: 82 A
NA2XH 4x25 mm2
Nexans ref. 10588804 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey
- Number of cores: 4
- Conductor cross-section: 25 mm²
- Nominal outer diameter: 22.3 mm
- Approximate weight: 660 kg/km
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Permissible current rating in open air: 97 A
- Permissible current rating when buried: 82 A
NA2XH 5x25 mm2
Nexans ref. 10588810 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey, black
- Number of cores: 5
- Conductor cross-section: 25 mm²
- Nominal outer diameter: 24.4 mm
- Approximate weight: 780 kg/km
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Permissible current rating in open air: 97 A
- Permissible current rating when buried: 82 A
NA2XH 3x35 mm2
Nexans ref. 10588765 - Country ref. TR
- Packaging: Drum
- Core identification: Brown, black, grey
- Number of cores: 3
- Conductor cross-section: 35 mm²
- Nominal outer diameter: 22.0 mm
- Approximate weight: 660 kg/km
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Permissible current rating in open air: 120 A
- Permissible current rating when buried: 98 A
NA2XH 4x35 mm2
Nexans ref. 10588805 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey
- Number of cores: 4
- Conductor cross-section: 35 mm²
- Nominal outer diameter: 24.2 mm
- Approximate weight: 800 kg/km
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Permissible current rating in open air: 120 A
- Permissible current rating when buried: 98 A
NA2XH 5x35 mm2
Nexans ref. 10588811 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey, black
- Number of cores: 5
- Conductor cross-section: 35 mm²
- Nominal outer diameter: 26.5 mm
- Approximate weight: 950 kg/km
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Permissible current rating in open air: 120 A
- Permissible current rating when buried: 98 A
NA2XH 3x50 mm2
Nexans ref. 10588801 - Country ref. TR
- Packaging: Drum
- Core identification: Brown, black, grey
- Number of cores: 3
- Conductor cross-section: 50 mm²
- Nominal outer diameter: 24.8 mm
- Approximate weight: 860 kg/km
- Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
- Permissible current rating in open air: 146 A
- Permissible current rating when buried: 117 A
NA2XH 4x50 mm2
Nexans ref. 10588806 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey
- Number of cores: 4
- Conductor cross-section: 50 mm²
- Nominal outer diameter: 27.5 mm
- Approximate weight: 1050 kg/km
- Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
- Permissible current rating in open air: 146 A
- Permissible current rating when buried: 117 A
NA2XH 5x50 mm2
Nexans ref. 10588809 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey, black
- Number of cores: 5
- Conductor cross-section: 50 mm²
- Nominal outer diameter: 30.4 mm
- Approximate weight: 1260 kg/km
- Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
- Permissible current rating in open air: 146 A
- Permissible current rating when buried: 117 A
NA2XH 3x70 mm2
Nexans ref. 10588802 - Country ref. TR
- Packaging: Drum
- Core identification: Brown, black, grey
- Number of cores: 3
- Conductor cross-section: 70 mm²
- Nominal outer diameter: 29.7 mm
- Approximate weight: 1180 kg/km
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- Permissible current rating in open air: 187 A
- Permissible current rating when buried: 144 A
NA2XH 4x70 mm2
Nexans ref. 10588807 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey
- Number of cores: 4
- Conductor cross-section: 70 mm²
- Nominal outer diameter: 32.9 mm
- Approximate weight: 1440 kg/km
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- Permissible current rating in open air: 187 A
- Permissible current rating when buried: 144 A
NA2XH 5x70 mm2
Nexans ref. 10588813 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey, black
- Number of cores: 5
- Conductor cross-section: 70 mm²
- Nominal outer diameter: 36.5 mm
- Approximate weight: 1760 kg/km
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- Permissible current rating in open air: 187 A
- Permissible current rating when buried: 144 A
NA2XH 3x95 mm2
Nexans ref. 10588803 - Country ref. TR
- Packaging: Drum
- Core identification: Brown, black, grey
- Number of cores: 3
- Conductor cross-section: 95 mm²
- Nominal outer diameter: 32.7 mm
- Approximate weight: 1530 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- Permissible current rating in open air: 227 A
- Permissible current rating when buried: 172 A
NA2XH 4x95 mm2
Nexans ref. 10588808 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey
- Number of cores: 4
- Conductor cross-section: 95 mm²
- Nominal outer diameter: 36.5 mm
- Approximate weight: 1870 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- Permissible current rating in open air: 227 A
- Permissible current rating when buried: 172 A
NA2XH 5x95 mm2
Nexans ref. 10588812 - Country ref. TR
- Packaging: Drum
- Core identification: Blue, brown, black, grey, black
- Number of cores: 5
- Conductor cross-section: 95 mm²
- Nominal outer diameter: 40.5 mm
- Approximate weight: 2280 kg/km
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- Permissible current rating in open air: 227 A
- Permissible current rating when buried: 172 A
Description
Description
Standards
-
ProductIEC 60502-1
Application
Used in energy networks in hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire
Construction
- Conductor:Aluminium
- Insulation:XLPE
- Filler:LSZH
- Outer sheath:LSZH
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania