N2XRH 4x50 mm2
N2XRH 4x50 mm2
0.6/1 kV XLPE insulated steel wire armoured multi-core cables with copper conductor
Read more- Nexans ref. : 10579525
- Country ref. : TR
- EAN : 8680969221658
Description
Description
Standards
-
ProductIEC 60502-1
-
NationalTS IEC 60502
Application
Used in energy networks in hotels, schools, tunnels, high constructions,hospitals, power plants, data processing centers, business centers where there is a risk of fire
Construction
- Conductor:Copper
- Insulatıon:XLPE
- Filler:LSZH
- Armour:Single layer galvanized round steel wires
- Outer Sheath:LSZH
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Galvanised round steel wires
Conductor flexibility
Stranded class 2
Conductor material
Copper
Conductor shape
Circular stranded (RM)
Core identification
-
Halogen free
IEC 60754-1
Insulation
XLPE (Cross-linked Polyethylene)
Material of filler / inner sheath
Halogen free filling
Outer sheath
LSZH
Sheath colour
Black
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
4 mm²
Approximate weight
2910 kg/km
Nominal outer diameter
31.8 mm
Number of cores
4
Electrical characteristics
Electrical characteristics
Conductor electrical resistance
- Ohm/km
Permissible current rating in open air
192 A
Permissible current rating when buried
153 A
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Mechanical resistance to impacts
Good
Usage characteristics
Usage characteristics
Bending factor when laying
8 (xD)
Flame retardant
IEC 60332-3 Cat. C
Gases corrosivity
IEC 60754-2
Max. conductor temperature in service
90 °C
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Smoke density
IEC 61034
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1001041-TRDE
- Certification Date : 1/18/24
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 1008
- Declared performance : Dca-s2,d2,a2