NYCY 4x6/6 mm2
NYCY 4x6/6 mm2
0,6/1 kV PVC insulated, concentric copper wire screened, multi core PVC sheathed cable with copper conductors
Read more- Nexans ref. : 10545839
- Country ref. : TR
- EAN : 8680969114196
Description
Description
Standards
-
NationalTS IEC 60502
Application:
Mainly laid underground in populated areas. In case of mechanical damage the screen prevents any damage due to power leak to the surrounding area.
Construction:
- Conductor:Copper
- Insulatıon:PVC
- Filler
- Concentric screen:Copper wires + copper tape
- Outer Sheath:PVC
Marking:
<>TSE<> NEXANS TS IEC 60502 YVCV Number of cores x cross section 0.6/1 kV ''YEAR''
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Insulation
PVC
Material of filler / inner sheath
Butyl + PVC
Outer sheath
PVC
Conductor flexibility
Stranded class 2
Conductor shape
Circular stranded (RM)
Core identification
Blue, brown, black, grey
Screen
Concentric copper
Sheath colour
Black
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Approximate weight
600 kg/km
Conductor cross-section
6 mm²
Neutral conductor section (when smaller)
- mm²
Nominal outer diameter
18.0 mm
Number of cores
4
Screen section
6 mm²
Electrical characteristics
Electrical characteristics
Conductor electrical resistance
3.08 Ohm/km
Permissible current rating in open air
43 A
Permissible current rating when buried
41 A
Permissible short circuit current screen 1s
- kA
Rated Voltage Uo/U (Um)
0,6/1 kV
Usage characteristics
Usage characteristics
Bending factor when installed
8 (xD)
Flame retardant
IEC 60332-1-2
Maximum operating temperature
70 °C
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
160 °C
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1000668-TRDE
- Certification Date : 3/14/18
- AVCP (Assessment and Verification of Constancy of Performance) : System 4
- Declared performance : Fca