CU/XLPE/CTS/LSZH/AWA/MDPE 1x185 mm2
CU/XLPE/CTS/LSZH/AWA/MDPE 1x185 mm2
12.7/22 kV XLPE insulated aluminium wire armoured, single core PE sheathed cables with copper conductor
Read more- Nexans ref. : 10550704
- Country ref. : TR
- EAN : 8680969122412
Description
Description
Standards
-
ProductBS 6622
Application:
These are cables with low dielectric losses used in energy networks with sudden load changes where mechanical stresses expected. Laid in residential or industrial areas, underground or in ducts.
Construction:
- Conductor:copper
- Conductor screen:Semi-conducting compound(XLPE)
- Insulation:XLPE
- Insulation screen:Semi-conducting compound(XLPE)
- Semi-conducting tape:Crape paper
- Metallic screen:Copper tape
- Separation sheath:LSZH
- Wire armour:Single layer aluminium wire
- Outer sheath:MDPE
Marking
ELECTRIC CABLE 22000 V BS 6622 NEXANS i Number of cores x cross section ''YEAR''
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Circular stranded (RM)
Material of the inner semi-conductor
XLPE
Insulation
XLPE (chemical)
Material of the external semi-conductor
XLPE
Screen
Copper tape
Armour type
Single layer of aluminium wires
Outer sheath
PE
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Conductor cross-section
185 mm²
Nominal outer diameter
40.0 mm
Approximate weight
3000 kg/km
Delivery reel size for 1000m
- cm
Screen section
- mm²
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
12.7 / 22 (24) kV
Max. DC resistance of the conductor at 20°C
0.099 Ohm/km
Approx. inductance, flat formation
0.56 mH/km
Approx. inductance, trefoil formation
0.37 mH/km
Nominal phase capacitance
0.27 µF / km
Perm. current rating buried 20°C - flat formation
410 A
Perm. current rating buried 20°C - trefoil formation
406 A
Perm. current rating in air 30°C - flat formation
637 A
Perm. current rating in air 30°C - trefoil formation
543 A
Permissible short circuit current conductor 1s
26.5 kA
Permissible short circuit current screen 1s
.96 kA
Mechanical characteristics
Mechanical characteristics
Mechanical resistance to impacts
Good
Usage characteristics
Usage characteristics
Packaging
Reel
Length
- m
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2
Bending factor when laying
15 (xD)
Max. conductor temperature in service
90 °C
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1000742-TRDE
- Certification Date : 9/28/18
- AVCP (Assessment and Verification of Constancy of Performance) : System 4
- Declared performance : Fca
Our websites