CU/XLPE/CWS/LSZH/SWA/LSZH 3x95/16 mm2

Description

Description

Standards

  • Product
    BS 7835

Application

Suitable for installations in energy networks where for safety reasons low smoke halogen free and flam retardant cables are specified. The cable is suitable for installation undergorund, in ducts or in air.

Construction

  1. Conductor: Stranded annealed round plain copper (Class 2)
  2. Conductor screen: Extruded semi-conductor
  3. Insulation: Cross-linked polyethylene (XLPE)
  4. Insulation screen: Extruded semi-conductor (Fixed Bonded), copper wires with counter helix of copper tape
  5. Assembling: Inner covering acting as a filler with practically zero thickness
  6. Seperation sheath: Low smoke, zero halogen (LSZH) coloured natural
  7. Metallic armour: Galvanized steel wires (GSWA)
  8. Protective sheath: Low smoke, zero halogen (LSZH) coloured black

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Material of the inner semi-conductor
XLPE
Insulation
XLPE
Material of the external semi-conductor
XLPE
Screen
Extruded semi-conductor, bare copper tape
Armour type
Galvanized steel wires
Outer sheath
LSZH
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
95 mm²
Nominal outer diameter
55.2 mm
Approximate weight
6820 kg/km
Delivery reel size for 1000m
- cm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
3.6/6 kV
Max. DC resistance of the conductor at 20°C
0.193 Ohm/km
Nominal inductance
- mH/km
Nominal phase capacitance
- µF / km
Perm. current rating buried 20°C - flat formation
263 A
Perm. current rating in air 30°C - flat formation
307 A
Permissible short circuit current conductor 1s
13.6 kA
Permissible short circuit current screen 1s
- kA

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-3 Cat. C
Bending factor when laying
- (xD)
Gases corrosivity
IEC 60754-1; IEC 60754-2
Max. conductor temperature in service
90 °C
Smoke density
IEC 61034-2 & EN 61034-2

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1001268-TRDE
  • Certification Date : 9/12/24
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 1008
  • Declared performance : Dca-s1,d2,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close