N2XS(FL)HR(AL)H 12.7/22 kV Cca Class

Products

N2XS(FL)HR(AL)H 1x300/25 mm2

Nexans ref. 10588670 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 300 mm²
  • Nominal outer sheath thickness: 1.8 mm
  • Impedance at 50 Hz : 0.13 Ohm
  • Permissible current rating buried 20°C: 526 A
  • Short Circuit Current 0,3 s Max : 78.3 kA
  • Short Circuit Current 1 s Max : 42.9 kA

 

N2XS(FL)HR(AL)H 1x630/35 mm2

Nexans ref. 10588671 - Country ref. TR

  • Packaging: Drum (1000m)
  • Conductor cross-section: 630 mm²
  • Nominal outer sheath thickness: 2.04 mm
  • Impedance at 50 Hz : 0.1 Ohm
  • Permissible current rating buried 20°C: 774 A
  • Short Circuit Current 0,3 s Max : 164.5 kA
  • Short Circuit Current 1 s Max : 90.1 kA

 

Description

Description

Standards

  • Product
    IEC 60228; IEC 60502-2
  • Test
    IEC 60332-3-24; IEC 60754-1; IEC 60754-2; IEC 61034

Application

These are cables with low dielectric losses used in energy network with sudden load changes. Laid in residental or industrial areas, underground or in ducts.

Construction

  1. Conductor: Stranded annealed round plain copper (Class 2)
  2. Conductor screen : Extruded semi-conductor
  3. Insulation : Cross-linked polyethylene (XLPE)
  4. Insulation screen: Extruded semi-conductor (Fixed Bonded)
    Water swelling tape (Semi-conductive)
    Copper wires with counter helix of copper tape
  5. Radial Water Barrier Layer
    Longitudinal Aluminium Foil
    Separation sheath sticking to the foil
    Low smoke, zero halogen (LSZH)
  6. Metallic armour: Aluminium wires (AWA)
  7. Protective sheath : Low smoke, zero halogen (LSZH) -  coloured red

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
Aluminium Wire
Conductor flexibility
Class 2
Halogen free
IEC 60754-1; IEC 60754-2
Longitudinally watertight
Yes
Radial waterproof
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Armour thickness
2.5 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12.7 / 22 (24) kV

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Flame retardant
IEC 60332-3 Cat. C
Longitudinal water tightness
Yes
Max. conductor temperature in service
90 °C
Radial water tightness
Yes
Smoke density
IEC 61034-2
U.V resistance
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close