NA2XS(F)2Y 1X400 mm2
NA2XS(F)2Y 1X400 mm2
19/33 kV XLPE insulated single core cables with aluminium conductor and PE outer sheath
Read more- Nexans ref. : 10574879
- Country ref. : TR
- EAN : 8680969196536
Description
Description
Standards
-
ProductIEC 60502-2
Application:
These are cables with low dielectric losses used in energy networks with sudden load changes and laid in residential or industrial areas, underground, or in ducts.
Construction:
- Conductor: Aluminium
- Conductor screen: Semi-conducting compound (XLPE)
- Insulation: XLPE
- Insulation screen: Semi-conducting compound (XLPE) + water swelling tape + copper wires with a counter helix of copper tape
- Outer sheath: MDPE
Marking:
NEXANS IEC 60502 NA2XS(F)2Y Number of cores x cross section 19/33 kV "YEAR"
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Conductor shape
Circular stranded (RM)
Material of the inner semi-conductor
XLPE
Insulation
XLPE (Cross-linked Polyethylene)
Material of the external semi-conductor
XLPE
Screen
Copper tape
Outer sheath
MDPE
Sheath colour
Red
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Conductor cross-section
400 mm²
Nominal outer diameter
47.0 mm
Approximate weight
2370 kg/km
Delivery reel size for 1000m
- cm
Screen section
12 mm²
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
19/33 kV
Max. DC resistance of the conductor at 20°C
0.078 Ohm/km
Approx. inductance, flat formation
- mH/km
Approx. inductance, trefoil formation
- mH/km
Nominal phase capacitance
- µF / km
Perm. current rating buried 20°C - flat formation
- A
Perm. current rating buried 20°C - trefoil formation
575 A
Perm. current rating in air 30°C - flat formation
- A
Perm. current rating in air 30°C - trefoil formation
673 A
Permissible short circuit current conductor 1s
37.6 kA
Permissible short circuit current screen 1s
- kA
Usage characteristics
Usage characteristics
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
12 (xD)
Longitudinal water tightness
Yes
Max. conductor temperature in service
90 °C
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1001118-TRDE
- Certification Date : 11/24/22
- AVCP (Assessment and Verification of Constancy of Performance) : System 4
- Declared performance : Fca