NA2XS(FL)H 1x240/25 mm2

Description

Description

Standards

  • Product
    IEC 60502-2

Application:

These are cables with low dielectric losses used in energy network with sudden load changes. Laid in residental or industrial areas, underground or in ducts.

 

Construction:

  1. Conductor:Aluminium
  2. Conductor screen:Semi-conducting compound (XLPE)
  3. Insulation:XLPE
  4. Insulation screen:Semi-conducting compound (XLPE) + water swelling tape + copper wires with counter helix of copper tape
  5. Outer sheath: Longitudinal Aluminium foil sticking to protective sheath LSZH

 

Marking:

NEXANS  IEC 60502 NA2XS(FL)H Number of cores x cross section 12/20 kV  "YEAR" Dca,s2,d2,a2 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Material of the inner semi-conductor
XLPE
Insulation
XLPE
Material of the external semi-conductor
XLPE
Screen
Copper wire + copper tape
Outer sheath
LSZH
Conductor flexibility
Class 2
Halogen free
IEC 60754-1; IEC 60754-2
Longitudinally watertight
Yes
Radial waterproof
Yes
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
240 mm²
Nominal outer diameter
90.0 mm
Approximate weight
- kg/km
Delivery reel size for 1000m
- cm
Screen section
35 mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12/20 kV
Max. DC resistance of the conductor at 20°C
- Ohm/km
Characteristic impedance
- Ohm
Perm. current rating buried 20°C - flat formation
367 A
Perm. current rating in air 30°C - flat formation
593 A
Permissible short circuit current conductor 1s
- kA
Permissible short circuit current screen 1s
- kA
Reactance at 50 Hz
- Ohm/km
Voltage Drop
- V/A.km

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
12 (xD)
Flame retardant
IEC 60332-3 Cat. C
Gases corrosivity
IEC 60754-1; IEC 60754-2
Max. conductor temperature in service
0 °C
Smoke density
IEC 61034-2

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1001205-TRDE
  • Certification Date : 12/15/23
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 1008
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close