H1Z2Z2-K 1x120 mm2

Description

Description

Standards

  • Product
    EN 50618

Application:

These state-of-art AC 1.0/1.0 and DC 1.5kV cross-linked cables offer exceptional performances, easy installation and long-term reliability for solar plant. They link photovoltaic panels for Utility-Scale solar plants or rooftops, and also connect them to the array box (if existing), or potentially to the inverter. 

Desgination: H1Z2Z2-K

Standard: EN 50618

Current Rating Temperature

Ambient temperature = 60°C

Maximum conductor temperature = 120°C

Water Resistant to AD8 According to EN 50525-2-21, Annex E

 

Construction: 

  1. Conductor: Flexible tinned copper, class 5 according to IEC 60228
  2. Insulation: Cross-linked halogen-free (XL-HFFR)
  3. Outer Sheath: Cross-linked halogen-free (XL-HFFR)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Tin Coated Copper Class 5 acc. To EN 60228
Insulation
Cross-linked (XL) HFFR acc. to EN 60811 and EN 60216-1-2
Halogen free
IEC 60754-1
Conductor flexibility
Flexible class 5
Outer sheath
Cross-linked (XL) HFFR acc. to EN 60811 and EN 60216-1-2
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
120 mm²
Nominal outer diameter
20.5 mm
Approximate weight
1180 kg/km
Conductor diameter (mm)
-
Nominal insulation thickness
1.2 mm
Nominal outer sheath thickness
1.01 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
1.0/1.0 (1.2) kV AC 1.5/1.5 (1.8) kV DC
Max. DC resistance of the conductor at 20°C
0.164 Ohm/km
Permissible current rating in air 60°C
488 A
Permissible current rating on a tray 60°C
- A

Usage characteristics

Usage characteristics

Flame retardant
IEC 60332-1-2
Operating temperature, range
-40 ... 90 °C
Short-circuit max. conductor temperature
250 °C
Smoke density
IEC 61034-2
Gases corrosivity
IEC 60754-2
Max. conductor temperature in service
120 °C
Ozone resistance
EN 50396:2005
Resistance to vibrations
Condition AH 3 (sever industrial conditions) acc. to HD 60364-5-52
U.V resistance
EN 50289-4-17 method A, for 720h. Nexans prestige test 4000h
Water proof
Passed 100 days 50°C water immersion test of EN 50525-2-21 annex D and E
Weather resistance
Excellent

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1001155-TRTU
  • Certification Date : 9/9/24
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 1008
  • Declared performance : Dca-s1,d2,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close