CU/XLPE/AWA/LSZH 1x630 mm2

Description

Description

Standards

  • International
    IEC 60502
  • National
    BS 6724

Application:

Used in energy networks in hotels, schools, tunnels, high constructions,hospitals, power plants, data processing centers, business centers where there is a risk of fire

Construction:

  1. Conductor:Copper
  2. Insulation:XLPE
  3. Inner sheath:LSZH
  4. Armour:Single layer Aluminium wire
  5. Outer sheath:LSZH

 

Marking

ELECTRIC CABLE  600/1000 V  BS 6724  H  NEXANS i 

Number of cores  x cross section  "YEAR"  BASEC

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor shape
Circular stranded (RM)
Conductor material
Copper
Insulation
XLPE (Cross-linked Polyethylene)
Core identification
Brown
Armour type
Aluminium Wire
Outer sheath
LSZH
Conductor flexibility
Stranded class 2
Halogen free
IEC 60754-1
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
630 mm²
Outer Diameter
45 mm
Approximate weight
6750 kg/km
Number of cores
1

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.028 Ohm/km
Perm. current rating in air 30°C - flat formation
992 A
Permissible current rating clipped direct
861 A
Permissible short circuit current conductor 1s
90.1 kA
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Short-circuit max. conductor temperature
250 °C
Operating temperature, range
-20 ... 60 °C
Bending factor when laying
15 (xD)
Flame retardant
IEC 60332-3 Cat. C
Gases corrosivity
IEC 60754-2
Max. conductor temperature in service
90 °C
Smoke density
IEC 61034
U.V resistance
Yes

Resources

Resources

Current capacity table XLPE insulation single core three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section A1 Insulated conductors in conduit in a thermally insulated wall B1 Insulated conductors in conduit on a wooden wall C Single-core or multi-core cable on a wooden wall D1 Single-core or Multi-core cable in ducts in the ground D2 Single-core or Multi-core cables designed to be buried directly in the ground F Single-core flat cables, touching in free air F Single-core trefoil cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
630.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1151.0 942.0 1088.0 899.0

Declaration of Performance

  • Declaration of Performance n� : 1000682-TRDE
  • Certification Date : 3/3/20
  • AVCP (Assessment and Verification of Constancy of Performance) : System 1+
  • Notified body : 1008
  • Declared performance : Cca-s1,d2,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*