- Newsroom
- Products
- Your Business
- Tools & Resources
- About Nexans
- People & Careers
- Documents
- Differentiated Offers
- CSR
- Search
- Contact us
- Compare
- Sign in
N2XS(F)H 1X185/25 mm2
N2XS(F)H 1X185/25 mm2
6.35/11 kV XLPE insulated single core cables with copper conductor and LSZH outer sheath
Read more- Nexans ref. : 10574929
- Country ref. : TR
- EAN : 8680969200950
Description
Description
Standards
-
ProductIEC 60502-2
Application:
These are cables with low dielectric losses used in energy network with sudden load changes. Laid in residental or industrial areas, underground or in ducts.
Construction:
- Conductor:Copper
- Conductor screen:Semi-conducting compound (XLPE)
- Insulation:XLPE
- Insulation screen:Semi-conducting compound (XLPE) + water swelling tape + copper wires with counter helix of copper tape
- Outer sheath: LSZH
Marking:
NEXANS IEC 60502 N2XS(F)H Number of cores x cross section 6.35/11 kV "YEAR"
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Circular compacted
Material of the inner semi-conductor
XLPE
Insulation
XLPE (Cross-linked Polyethylene)
Material of the external semi-conductor
XLPE
Screen
Copper wire + copper tape
Outer sheath
LSZH
Conductor flexibility
Stranded class 2
Halogen free
IEC 60754-1; IEC 60754-2
Longitudinally watertight
Yes
Sheath colour
Red
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Conductor cross-section
185 mm²
Nominal outer diameter
30.0 mm
Approximate weight
2340 kg/km
Delivery reel size for 1000m
- cm
Screen section
25 mm²
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
6.35 / 11 kV
Max. DC resistance of the conductor at 20°C
0.0991 Ohm/km
Characteristic impedance
0 Ohm
Perm. current rating buried 20°C - flat formation
406 A
Perm. current rating in air 30°C - flat formation
637 A
Permissible short circuit current conductor 1s
26.5 kA
Permissible short circuit current screen 1s
- kA
Reactance at 50 Hz
0.1 Ohm/km
Voltage Drop
0.3 V/A.km
Usage characteristics
Usage characteristics
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
12 (xD)
Flame retardant
IEC 60332-3 Cat. C
Gases corrosivity
IEC 60754-1; IEC 60754-2
Max. conductor temperature in service
90 °C
Smoke density
IEC 61034-2
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1001111-TRDE
- Certification Date : 9/4/23
- AVCP (Assessment and Verification of Constancy of Performance) : System 1+
- Notified body : 1008
- Declared performance : B2ca-s1,d1,a1
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania